High-precision grid analysis within the EtherCAT Terminal system

Electrical Technology

New Beckhoff EL3783 power monitoring oversampling terminal for high-resolution diagnostics of alternating voltages up to 690 V AC .

Conventional automation and power measurement technology are increasingly converging. With the integration of the new Beckhoff EL3783 oversampling terminal for power monitoring into standard control systems, high-precision grid analysis becomes available for power-generating systems. Most importantly, three-phase AC voltage systems up to 690 V can be analysed simultaneously on six channels and with 20 ksamples/s directly in the PLC. 

For each of the three phases, the EL3783 EtherCAT Terminal from Beckhoff samples voltages up to 400/690 Vrms and currents up to one or five Arms as instantaneous values with 16 bit resolution. The six terminal channels are evaluated simultaneously based on the EtherCAT oversampling principle, with a temporal resolution of 50 μs, i.e. significantly faster than the cycle time of the controller. Using the EtherCAT distributed clocks functionality, it is also possible to measure synchronously (<< 1 μs) with other EtherCAT devices in systems of virtually any size and precisely detect propagating grid faults, for example. 

Extensive data with relevant details are available in the control system if true RMS and performance calculations or complex user-specific algorithms are used to analyse the voltage and current curves, for instance. In addition, the EL3783 EtherCAT Terminal achieves 650 percent of the nominal one-ampere measuring range through automaticcurrent range switching, offering high accuracy with a maximum measurement error of only 0.2 percent (of the full scale value). 

In conjunction with TF3650, the TwinCAT 3 Power Monitoring library, the EL3783 Terminal represents a highly dynamic measurement system for detailed network analysis that is seamlessly integrated into standard PC-based control technology. In this way, requirements for network supporting measures in the event of voltage drops (LVRT, Low Voltage Ride Through) can be identified, for example, or harmonics analysis can be used to implement condition monitoring without additional costs for acceleration sensors.

vThe EL3783 power monitoring oversampling terminal from Beckhoff provides detailed current and voltage values for three-phase power grids up to 690 V AC, while meeting demanding requirements in wind turbine applications. Picture credits: Beckhoff Automation in ranking the highest automated countries in the world. 

Details:  Beckhoff Automation

PH: 09 281 2736

Email:  info@beckhoff.co.nz

Publishing Information
Page Number:
30
Related Articles
element14 now stocking Microchip’s new PIC32CM PL10 MCUs
element14 has announced the immediate availability of the newly launched PIC32CM PL10 microcontrollers (MCUs) from Microchip Technology. As the latest addition to Microchip’s PIC32C family of Arm...
element14 Community launches smart industry design challenge
element14 has launched its latest design competition, inviting engineers, makers and technology enthusiasts to develop smart industry projects focused on production monitoring, uptime optimisation...
element14’s Top Tech Voices returns exploring brain health and sustainable technology
element14's award-winning podcast series Top Tech Voices continues its second season with two thought-provoking episodes examining how technology influences both human wellbeing and planetary...